What do S, SDR and PN mean?
PPRC pipes are defined by outside diameter (d) and wall thickness (e). SDR (standard dimension ratio) is the ratio of outside diameter to wall thickness: SDR = d / e. The pipe series S follows from S = (SDR − 1) / 2. All diameters with the same SDR have the same internal pressure resistance; the wall grows in proportion to the diameter.
PN (nominal pressure) is a trade class in bar for water at 20 °C. The PN label depends on the safety factor chosen and can differ between manufacturers: some catalogues mark an SDR 7.4 pipe as PN16, others as PN20. Always state the S or SDR value next to PN in orders and project documents.
Wall thickness and inner diameter chart (Ø20–Ø110)
| Outside diameter d (mm) | Approx. inch | S5 · SDR 11 PN10 | S3.2 · SDR 7.4 PN16 | S2.5 · SDR 6 PN20 | S2 · SDR 5 PN25 |
|---|---|---|---|---|---|
| 20 | 1/2" | 1.9 / 16.2 | 2.8 / 14.4 | 3.4 / 13.2 | 4.1 / 11.8 |
| 25 | 3/4" | 2.3 / 20.4 | 3.5 / 18.0 | 4.2 / 16.6 | 5.1 / 14.8 |
| 32 | 1" | 2.9 / 26.2 | 4.4 / 23.2 | 5.4 / 21.2 | 6.5 / 19.0 |
| 40 | 1 1/4" | 3.7 / 32.6 | 5.5 / 29.0 | 6.7 / 26.6 | 8.1 / 23.8 |
| 50 | 1 1/2" | 4.6 / 40.8 | 6.9 / 36.2 | 8.3 / 33.4 | 10.1 / 29.8 |
| 63 | 2" | 5.8 / 51.4 | 8.6 / 45.8 | 10.5 / 42.0 | 12.7 / 37.6 |
| 75 | 2 1/2" | 6.8 / 61.4 | 10.3 / 54.4 | 12.5 / 50.0 | 15.1 / 44.8 |
| 90 | 3" | 8.2 / 73.6 | 12.3 / 65.4 | 15.0 / 60.0 | 18.1 / 53.8 |
| 110 | 4" | 10.0 / 90.0 | 15.1 / 79.8 | 18.3 / 73.4 | 22.1 / 65.8 |
- di = d − 2e, calculated from nominal values without tolerances.
- Some manufacturers list 2.0 mm wall thickness for Ø20 SDR 11.
- Some manufacturers supply the PN25 class as a glass-fibre reinforced composite pipe instead of solid-wall SDR 5; dimensions then follow the manufacturer catalogue.
- Inch equivalents are approximate trade equivalents; PPRC pipes are sized by metric outside diameter.
Typical fields of application
| Pipe series | Typical use |
|---|---|
| S5 · SDR 11 | Cold water and floor heating |
| S3.2 · SDR 7.4 | Hot water and floor heating |
| S2.5 · SDR 6 | Hot water and central heating |
Choosing the pipe series by application class
ISO 15874 groups PPRC systems into application classes by service temperature profile, with a 50-year design life. The table shows the pipe series required for 8 bar and 10 bar operating pressure.
| Application class | Use | 8 bar | 10 bar |
|---|---|---|---|
| 1 | Hot water supply 60 °C | S3.2 · SDR 7.4 | S2.5 · SDR 6 |
| 2 | Hot water supply 70 °C | S2.5 · SDR 6 | S2 · SDR 5 |
| 4 | Floor heating and low-temperature radiators | S3.2 · SDR 7.4 | S3.2 · SDR 7.4 |
| 5 | High-temperature radiators | S2 · SDR 5 | — |
Quick selection notes
- Assess pressure and temperature together: the permissible operating pressure falls as temperature rises.
- Pipes of different SDR share the same outside diameter, so they weld to the same socket fittings.
- Thermal elongation is significant on hot water lines; see the installation guide for the expansion calculation. Installation guide
Sources
Values were compiled from published documents based on the standards below and cross-checked against each other. Full standard texts are paid, so manufacturer catalogues declaring conformity to them were also used.
- DIN 8077:2008-09 – polypropylene pipes, dimensions (table of contents, DIN)
- Peštan – Technical catalogue, pipes and fittings DN16–630 (tube geometry table, expansion coefficient, support spacing)
- Uplast – PPRC pipe and fitting systems technical catalogue (wall thickness table S5–S2, application classes)
- Wavin – Pilsa piping systems technical and installation manual (support spacing, expansion, pressure test)
This page is for information only. The project specification, local regulations and the instructions of the pipe and fitting manufacturer always take precedence.